SWA (Steel wire armoured) Armoured Copper/Aluminum Power Cable low voltage

SWA (Steel wire armoured) Armoured Copper/Aluminum Power Cable low voltage

SWA (Steel wire armoured) Armoured Copper/Aluminum Power Cable low voltage

Inquiry Now

Application

Cu/XLPE/PVC/SWA/PVC power cable may be used for fixed installation indoors and outdoors in cable ducts or directly in the ground. The steel wire armoured cable is the accepted standard for underground installations, designed for use in mains supply electricity. These cables are provided with mechanical protection and are therefore suitable for external use, direct burial and areas where sudden mechanical stress are expected. SWA Cable is one of our most popular cables from small projects in the garden for landscapers to large infrastructure projects.


Technical Information

Conductor Material:Copper, IEC60228

Conductor Shape:

1.Smm2 up to 16mm2Circular

25mm2 up to 400mm2  Sector-shaped

Conductor FlexibilityStranded class 2

Insulation:XLPE (Cross-linked Polyethylene), IEC60502

Armour Type:Galvanized steel wires

Outer Sheath:PVC,IEC60502

Inner Sheath:PVC,IEC60502

Sheath Colour:Black

Rated Voltage Uo/U (Um):600/1000V, BS5467

Installation Temperature:

Minimum: 0°c Maximum: 60°C

Installation Type:Outdoor Direct burial

Operating Temperature:Maximum: 90°C

Short-circuit Maximum Conductor Temperature:250°C

Flame Retardant:IEC 60332-1

Bending Radius:

1.5mm2 up to 16mm2 = 6 x 0

25mm2 up to 400mm2 = 8 x 0

 

Type

No. of cores

Nom. Cross-section of conductor

Copper conductor

Aluminum conductor

(mm2)

YJV  YJY

-

1

1.5-800

-

YJLV  YJLY

2.5-800

YJV22  YJV23

YJLV22  YJLY23

10-800

YJV  YJY

-

2

1.5-300

-

YJLV  YJLY

2.5-300

YJV22  YJV23

YJLV22  YJLY23

4.0-300

YJV32  YJV33

YJLV32  YJLY33

10-300

YJV  YJY

-

3

1.5-400

-

YJLV  YJLY

2.5-400

YJV22  YJV23

YJLV22  YJLY23

4.0-400

YJV32  YJV33

YJLV32  YJLY33

10-400

YJV  YJY

-

4

1.5-400

-

YJLV YJLY

2.5-400

YJV22  YJV23

YJLV22  YJLY23

4.0-400

YJV32  YJV33

YJLV32  YJLY33

10-400

YJV  YJY

-

3+1

1.5-400

-

YJLV  YJLY

4.0-400

YJV22  YJV23

YJLV22  YJLY23

4. 0-400

YJV32  YJV33

YJLV32  YJLY33

10-400

YJV  YJY

-

5

1.5-400

-

YJLV  YJLY

2.5-400

YJV22  YJV23

YJLV22  YJLY23

4.0-400

YJV32  YJV33

YJLV32  YJLY33

10-400

YJV  YJY

-

4+1

1.5-400

-

YJLV  YJLY

4.0-400

YJV22  YJV23

YJLV22  YJLY23

4. 0-400

YJV32  YJV33

YJLV32  YJLY33

10-400

YJV  YJY

-

3+2

1.5-400

-

YJLV  YJLY

4.0-400

YJV22  YJV23

YJLV22  YJLY23

4. 0-400

YJV32  YJV33

YJLV32  YJLY33

10-400

The armoured single core cables are used for D.C. system only. As for A.C. system,non-magnetic armour material should be used, or a magnetic isolation should be applied.

 

Type

Name

VV  VLV

Copper(aluminum)Conductor,PVC insulated and Sheathed Power Cable

VV22  VLV22

Copper(aluminum)Conductor,PVC insulated,Steel-tape Armoured,PVC Sheathed Power Cable

VV23 VLV23

Copper(aluminum)Conductor,PVC insulated,Steel-tape Armoured,PVC Sheathed Power Cable

VV32 VLV32

Copper(aluminum)Conductor,PVC insulated,Fine Steel-wire Armoured,PVC Sheathed Power Cable

VV33  VLV33

Copper(aluminum)Conductor,PVC insulated,PE Sheathed Power Cable

VV42  VLV42

Copper(aluminum)Conductor,PVC insulated,Thick Steel-wire Armoured, PVC Sheathed Power Cable

VV43   VLV43

Copper(aluminum)Conductor,PVC insulated,Thick Steel-wire Armoured, PE Sheathed Power Cable

Cu/XLPE/PVC/SWA/PVC SWA Armoured Power Cable 0.6/1kV

Cross section (mm2)

Stranding (mm)

Approx overall diameter            (m)

Max. DC-resist conductor 20 (ohm/km)

Current            rating laid   direct             (A)

4 x 1.5

7/0.53

12.88

12.1

32

4 x 2.5

7/0.67

14.43

7.41

42

4 x 4.0

7/0.85

16.87

4.61

55

4 x 6.0

7/1.04

17.87

3.08

69

4 x 10

7/1.35

20.1

1.83

92

4 x 16

7/1.70

22.4

1.15

119

4 x 25

7/2.14

27

0.727

152

4 x 35

7/2.52

30.1

0.524

182

4 x 50

19/1.78

31.5

0.387

217

4 x 70

19/2.14

37.4

0.268

266

4 x 95

19/2.52

40.9

0.193

319

4 x 120

37/2.03

46.6

0.153

363

4 x 150

37/2.25

50.2

0.124

406

4 x 185

37/2.52

55.8

0.0991

458

4 x 240

61/2.52

62.5

0.0754

529

4 x 300

61/2.85

67.4

0.0601

592

4 x 400

61/3.20

77

0.047

667

5 x 1.5

7/0.53

13.72

12.1

32

5 x 2.5

7/0.67

15.46

7.41

42

5 x 4.0

7/0.85

17.38

4.61

55

5 x 6.0

7/1.04

19.05

3.08

69

5 x 10

7/1.35

22.06

1.83

92

5 x 16

7/1.70

24.14

1.15

119

5 x 25

7/2.14

28.4

0.727

152

5 x 35

7/2.52

33

0.524

182

5 x 50

19/1.78

38

0.387

217

5 x 70

19/2.14

42.9

0.268

266

5 x 95

19/2.52

52.1

0.193

319


0.6/1.0kV AL/XLPE/PVC/Steel Wire  Armoured/PVC power cable  

Cable section

Nominal thickness insulation         (mm)

Nominal thickness of sheath           (mm)

Approx            overall diameter          (mm)

Max. DC-resist conductor           20 (Ω/km)

4x2.5mm2

0.8

1.8

16.7

12.1

4x4mm2

1

1.8

18.8

7.41

4x6mm2

1

1.8

20.1

4.61

4x10mm2

1

1.8

23.9

3.08

4x16mm2

1

1.8

26.4

1.91

4x25mm2

1.2

1.9

27.8

1.2

4x35mm2

1.2

2

30.2

0.868

4x50mm2

1.4

2.1

33.7

0.641

4x70mm2

1.4

2.3

38.3

0.443

4x95mm2

1.6

2.4

43.2

0.32

4x120mm2

1.6

2.6

47.8

0.253

4x150mm2

1.8

2.7

51.8

0.206

4x185mm2

2

2.9

56.9

0.164

4x240mm2

2.2

3.1

63.5

0.125

4x300mm2

2.4

3.4

71.1

0.1

4x400mm2

2.6

3.7

78.5

0.0778