Operate temperature: -60degree to+180degree Construction:conductor: tinned copper wire;insualtion: silicone rubber
Application
Silicone cables are employed where insulations are subjected to extreme changes in temperature.
They are heat resistant up to 180 Deg C, intermittently 220 Deg C.
Due to good resistance in all weather conditions these cables can also be employed at temperatures
as low as - 60 Deg C.
Upon and after combustion a residue of pure silica is produced and the cables continue to function.
However, it is usual to provide a glass braid around the cable to prevent a break down of the silica during
and after a fire. Silicone cables are halogen free and are most suitable for power plants. They have become
indispensable in a wide range of industrial sectors, in foundries, steel and hot rolling mills, cooking equipment,
cement, glass and ceramic factories, ship and aircraft construction, and oil burners.
Specification
Conductors: Flexible class 5 tinned copper conductors to BS 6360
Insulation: Silicone rubber:SIF
Treated glass fibre braid:SIF/ GL
Rated Voltage: 300/500V
Minimum bending radius 15*OD
Temp rating - 60 to + 180 Deg C
Available in various colours.
SIF /GL normally white.
180degree silicone high temperature cable | |||||
Cable Size (mm2) | Conductor structure (No./mm) | SIF | SIF / GL | ||
OD(mm) | Weight of cable (KG/KM) | OD(mm) | Weight of cable (KG/KM) | ||
0.5 | 16/0.20 | 2.1 | 8 | 2.6 | 12 |
0.75 | 24/0.20 | 2.4 | 11 | 2.9 | 16 |
1 | 32/0.20 | 2.5 | 14 | 3 | 18 |
1.5 | 30/0.25 | 2.8 | 19 | 3.3 | 23 |
2.5 | 50/0.25 | 3.4 | 30 | 3.9 | 35 |
4 | 56/0.30 | 4.2 | 48 | 4.7 | 53 |
6 | 84/0.30 | 5.2 | 71 | 5.7 | 77 |
10 | 80/0.40 | 7 | 120 | 7.5 | 129 |
16 | 126/0.40 | 8.4 | 180 | 8.9 | 198 |
25 | 196/0.40 | 10.3 | 290 | 10.8 | 302 |
35 | 270/0.40 | 11.6 | 400 | 12.1 | 413 |
50 | 396/0.40 | 13.9 | 550 | 14.4 | 578 |
70 | 360/0.50 | 16 | 750 | 16.5 | 815 |
95 | 475/0.50 | 18.4 | 1000 | 18.9 | 1100 |