3CORE ROUND CABLES FOR SUBMERSIBLE PUMPS(1100 VOLTS)
Double Sheathed Round 3 core cables are better suited for heavy duty application like sewage, slurry and dewatering pumps.
These conditions requires the seething to be able to with stand abrasion, prevent ingress of water along the interstices of the
cable and be resistant to acidic fluids and chemicals.
APPLICATION :
For continuous use in deep well to supply power to submersible pumps down to depths of 500 mtrs.
FEATURES & PROPERTIES :
Meets the requirement of CENELEC HD 22.1.S2, DIN VDE 0282 PART 810, IEC 245, CEI 20-19 & BS 6007, BS 6899.
Designed for heavy duty use.
Cur, tear & abrasion resistant.
Exceptional long term performance.
Excellent resistant to oils, chemicals,ozone & solvents.
Excellent Impact Resistant.
Excellent Weather Resistant.
Performs & Looks like Vulcanize Rubber.
Excellent Electrical Properties.
CONSTRUCTION :
Conductor : Finely stranded bare copper flexible conductor.
Insulation : Oil & water resistant thermoplastic rubber,
Sheath : Black heavy duty thermoplastic rubber.
Core Colours :
3core: Red ,Yellow and Blue.
3core: Black,Light Blue and Brown
3CORE ROUND CABLES FOR SUBMERSIBLE PUMPS(1100 VOLTS) | ||||||
Conductor | Insulation | Sheath | Conductor Resistance at 20℃ (max) | |||
Nominal Area | No.&Dia. of wire | Nominal Thickness | Nominal Core Dia. | Nominal Thickness | Approx. Overall Dia | |
mm2 | No./mm | mm | mm | mm | mm | Ω/km |
1.5 | 22/0.30 | 0.8 | 3.25 | 1.5 | 10 | 12.1 |
2.5 | 36/0.30 | 0.9 | 3.84 | 1.5 | 11 | 7.41 |
4 | 56/0.30 | 1 | 4.5 | 1.6 | 13 | 4.95 |
6 | 85/0.30 | 1 | 5.3 | 1.6 | 14.6 | 3.3 |
10 | 140/0.30 | 1 | 6.5 | 2 | 18 | 1.91 |
16 | 226/0.30 | 1 | 8 | 2 | 21.2 | 1.21 |
25 | 354/0.30 | 1.2 | 10.1 | 2.15 | 26 | 0.78 |
35 | 495/0.30 | 1.2 | 11.3 | 2.15 | 28.3 | 0.554 |
50 | 703/0.30 | 1.4 | 13.6 | 2.25 | 33.5 | 0.386 |
70 | 440/0.45 | 1.4 | 15.3 | 2.45 | 37.8 | 0.272 |
95 | 475/0.50 | 1.6 | 18 | 2.4 | 43.5 | 0.206 |